sediver_isolatorer Sediver_Härdat Glas
kN

IEC

Toughened Glass
Suspension Insulator
Ball and Socket type
 
Standard
Profile
 
Fog Type
Profile
CATALOGUE N°  
UF300CH195
CC024NI
 
UF300PK195
CC024NI
UF300PJ195
CC024NI
           
IEC class (1)  
U300B
 
U300BP
U300BP
MECHANICAL CHARACTERISTICS                
Minimum Mechanical Failing load

kN

300
 
300
 
300
DIMENSIONS                
Diameter
mm
330
   
380
 
320
 
Spacing
mm
195
   
195
 
195
 
Creepage distance
mm
485
   
690
 
595
 
Metal fitting size (2)
 
24
   
24
 
24
 
ELECTRICAL CHARACTERISTICS (3)                

Power frequency withstand voltage
-Dry one minute
-Wet one minute


kV
kV
85
50
   
100
55
 

85
50

 
Dry lightning impulse withstand voltage
kV
130
   
150
 
130
 
Puncture withstand voltage
kV
130
   
130
 
130
 
String values
   
 
PACKING AND SHIPPING DATA                
Approx. net weight
kg
10.9
   
15.3
 
11.1
 
No. of insulators per crate
 
5
   
3
 
5
 
Volume per crate
m3
0.11
   
0.9
 
0.11
 
Gross weight per crate
kg
57.5
   
48
 
58.5
 
No of insulators per pallet
 
45
   
54
 
45
 
Volume per pallet
m3
1.34
   
2.1
 
1.34
 
Gross weight per pallet
kg
555
   
950
 
551
 
Former designation  
F300/195
 
F300P/195
                 

Insulators with specific protection against corrosion are also available

(1) in accordance with IEC publication 60305
(2) in accordance with IEC publication 60120